Liquid Resistance Starter
ZDQ series Full Automatic Liquid Resistor Starters are new generation starting equipment that are developed for improving the starting characteristic of large- and medium-sized winding asynchronous motors. The principle of them is that the resistance value of liquid resistor being connected in series to rotor circuit is improved smoothly, so as to realize no-impact smooth starting.
Guangzhou Haoqing Mechanical And Electrical Equipment Co., Ltd. is one of the leading manufacturers and suppliers of liquid resistance starter in China. Welcome to buy high-grade liquid resistance starter made in China here from our factory. All customized products are with high quality and low price.
Liquid Resistance Starter
1.General Description
- ZDQ series Full Automatic Liquid Resistor Starters are new generation starting equipment that are developed for improving the starting characteristic of large- and medium-sized winding asynchronous motors. The principle of them is that the resistance value of liquid resistor being connected in series to rotor circuit is improved smoothly, so as to realize no-impact smooth starting. Because of a fair large thermal capacity of the liquid resistor, their starting times in a unit time are more than other kind of starting devices, such as frequency sensitive rheostat. The characteristics of them are better than that of frequency sensitive, oil immersed rheostat starters. They are easy in maintenance and operate with high operating characteristic. The starting equipment of ZDQ series are widely used in 100kw-6000kw winding motors for heavily starting ball grinders, air blowers, rolling mills, water pumps and stone breakers used in building materials and metallurgical and some other industries.
2.Main Technical Parameters:
- Starting current: Iq ≤1.3Ie
- Starting torque: Mq≤Me
- Starting times: 5-10 times in succession
2.1Main technical parameters of starters in different sizes
|
Model |
Suitable motor capacity (kW) |
Starting time (s) |
Temperature rise of liquid resistor (℃) |
Resistance(Ω)per phase |
|
ZDQ6-0.4 |
90~355 |
15 |
< 5 |
0.1-2 |
|
ZDQ6-0.6 |
380~570 |
15~25 |
< 5 |
0.2-3 |
|
ZDQ6-1 |
570~1250 |
15~25 |
< 8 |
0.4-3 |
|
ZDQ6-2 |
1400~2500 |
20~30 |
< 10 |
0.4-3 |
|
ZDQ6-3 |
2500~3000 |
30~50 |
< 10 |
0.4-3 |
|
ZDQ6-4 |
3000~6000 |
50~80 |
< 15 |
0.3-3 |
2.2 Normal working environment of starter
The ambient temperature range is –25℃ to +45℃ and the elevation height is no more than 2000 meters.
The relative humidity is no more than 90 percent. There are not any explosive dangers, conductive and serious corrosive dust in the medium.
There is no obvious impact vibration in installation site.
2.3 Electric source of starter (not including stator side electric source)
Four-wire three-phase system: AC 380V/220V 50Hz 20A
3.External View and Installation Dimensions

Installation dimensions:
|
Model |
Reference external dimensions (mm) |
Installation dimensions |
||||
|
A |
B |
C |
E |
F |
Φd |
|
|
ZDQ6-0.2 |
660 |
860 |
2000 |
360 |
740 |
12 |
|
ZDQ6-0.4, ZDQ6-0.4K |
800 |
860 |
2000 |
500 |
740 |
12 |
|
ZDQ6-0.6, ZDQ6-0.6K |
800 |
860 |
2000 |
500 |
740 |
12 |
|
ZDQ6-1 |
1000 |
960 |
2000 |
700 |
740 |
14 |
|
ZDQ6-2 |
1000 |
960 |
2000 |
900 |
740 |
14 |
|
ZDQ6-3 |
1400 |
1260 |
2000 |
1100 |
740 |
14 |
|
ZDQ6-4 |
1600 |
1260 |
2000 |
1100 |
740 |
14 |
4.Transportation and Hoisting
4.1 Impact shall be avoided during transporting and hoisting, so as not to make electric liquid cabinet be damaged and leak the liquid.
4.2 Inclination to vertical line should be less than 30°during hoisting.
5. Installation Requirements of Starter
5.1 It is suggested that liquid starting cabinet should be installed on the cement foundation where can drain.
5.2 The cabinet body should be installed as vertical as possible on horizontal plane.
5.3 The cabinet body should be installed right over the cable channel that is equipped with channel iron base according to its external dimensions
5.4 The cable of rotor of motor is connected to the starting plate on the rear side after running through a pipe.
6. Adjusting Method
6.1 Determinations of starting resistor
The resistance value RO of each phase of the resistor connected in series to circuit of motor rotor should be determined according to the following formula:

where
U2e: open-circuit voltage of rotor
I2e: Rated current of rotor
I1e: Rated current of stator
I1: Running current of stator
K: Constant (within the range of 1.1 to 1.3)
6.2 Preparation of liquid resistor
Hot Tags: liquid resistance starter, China liquid resistance starter manufacturers, suppliers, factory, DC Brushless Driver, Liquid Resistance Starter, Inverter For Low Voltage Asynchronous Motors, motor driving system, Liquid Resistance, Inverter